Sweltering summer heat at local hotel causes mass guest check out
Samantha received a frantic call from Javier, the building engineer at the Crestar Hotel, a 500-room luxury hotel, downtown Phoenix. Javier received early morning complaints from guests of seeming broken thermostats that kept his team busy.
By mid-morning, when call frequency increased and the complaints were more consistent about the lack of air conditioning, Javier decided to investigate the chiller system. He discovered that the flow rate was inconsistent and refused to remain at the desired set point.
By noon that day, room temperatures soared and a total of 125 guests checked out of the hotel. Some guests and staff suffered severe heat exhaustion as the hotel wasn’t able the keep up with the demand for water and fans. The hotel lost several hundred thousand dollars in one day.
Chillers or boilers and other HVAC systems require circulating coolant to function. If the coolant does not circulate at the proper rate, too much or too little heat will be exchanged, meaning the system will not properly control the temperature, thereby reducing energy efficiency.
Moreover, if the flow rate of an HVAC system is too high or too low it can also cause overheating or freezing damage.
Flow control typically requires a more complex control algorithm.
As a result, system integrators and panel builders typically use the Proportional, Integral, Derivative (PID) function within nano programmable logic controllers (PLCs).
PID control is a closed loop mathematical function. It works by:
Nano PLCs can easily implement PID to control the flow rate of coolant in Crestar Hotel’s chiller system.
The error between the setpoint and the feedback from an analog device can be fed into a PID function block. The output of the PID can then directly control an analog output to an electronic control valve.