Eaton Tripp Lite series metered outlet PDU, 3PH, 0U, NEMA L21-30P input, 6 ft cord, 8.6kW, 24A, 208V, 48 Outlets (36) C13 (6) C19 (6) 5-20R, TAA
Product Name |
Eaton Tripp Lite series metered outlet PDU
|
Catalog Number |
PDU3MV6L2130
|
UPC |
037332163875
|
Product Length/Depth |
2.65 in
|
Product Height |
70 in
|
Product Width |
2.2 in
|
Product Weight |
13.92 lb
|
Compliances |
FCC Class A
RoHS TAA Compliant |
Certifications |
RETIE
UL 62368-1 NOM |
Form factor |
0U (Vertical)
|
Package contents |
|
Operating Temperature |
32° to 104°F (0° to 40°C)
|
Mounting direction |
Vertical
|
Material |
Metal
|
Input connection |
NEMA L21-30P
|
Cord length |
6 ft
|
Amperage Rating |
24A
|
Electric current - max |
24
|
Phase |
3-Phase
|
Frequency rating |
50/60 Hz
|
Number of Outputs 5-20R |
6
|
Number of Outputs C13 |
36
|
Number of Outputs C19 |
9
|
Features |
Flex Center
|
Front Panel LCD Display |
Set of 3 digital current meters report input current in amps (L1, L2, L3)
|
Output Receptacles |
C13
C19 5-15/20R |
Overload protection |
Three 20A double-pole circuit breakers (1 per output phase)
|
Recommended electrical service |
Three-phase 30A 208V service
|
Reported load Segments |
Supports monitoring of input current per phase (13.8A balanced max per L1, L2 and L3); Outlets are color-coded and labeled for phase and load bank identification; Phase L1-L2 feeds black C13 & C19 outlets; Phase L2-L3 feeds dark-gray C13 & C19 outlets; Phase L3-L1 feeds light-gray C13 & C19 outlets; Phase L1-N feeds black 5-20R outlets; Phase L2-N feeds dark-gray 5-20R outlets; Phase L3-N feeds light-gray 5-20R outlets
|
Output Receptacles Details |
5-15/20R outlets provide 120V output; C13 and C19 outlets provide 208V output
|
Receptacles |
|
Input Cord Length |
6 ft
|
Product Features |
TAA Compliant
|
Amperage Rating Details |
Agency de-rated to 24A continuous
|
Operating elevation |
0-10000 ft. (0-3000 m)
|
Operating temperature range |
32° to 104°F (0° to 40°C)
|
Output nominal voltage |
208/120V
|
Relative humidity |
5% to 95% non-condensing
|
Form Factors Supported |
Vertical rackmount installation supported with included mounting brackets; supports toolless mounting in button-mount compatible racks
|
Output Capacity Details |
8.6kW (208V) total capacity; 13.9A (208V) max per output phase (L1-L2, L2-L3, L3-L1) / 16A (120V) max per output phase (L1, L2, L3); 12A max per C13 outlet; 16A max per 5-20R outlet
|
Storage temperature |
-22° to 140°F (-30° to 60°C)
|
Product Highlights |
Reports input current per-phase via built in current meters
48 outlets total; 36 C13 (208V), 6 C19 (208V) and 6 NEMA 5-15/20R (120V) TAA Compliant Toolless button-mount installation; cord retention brackets included Local Metered 8.6kW 3 Phase 208/120V PDU; 70 in. / 178cm 0U vertical rackmount NEMA L21-30P (3P+N+E) 208V 3 phase input; 6-ft. (1.83 m) line cord |
PDU Plug Type |
L21-30P
|
PDU Type |
Local metered
|
PDU Input Voltage |
208
|
PDU Form Factor |
Vertical (0U)
|
Support from Eaton